The safe isolation of plant and equipment · HSE guidance HSG253, second edition

Prove it before
you break it.

Below is a live fuel gas filter with a fault you cannot see. Isolate it, prove it, open it, hand it back. The plant answers to physics, and the debrief answers to the guidance, paragraph by paragraph.

DrawingHSG253-TR-001
TitleF-201 fuel gas filter · isolation for element change
P&ID revC
Clock06:30
StateIsolating

Select a valve on the drawing or in the certificate, then act on it. Every action costs clock time and moves real pressure.

Work order 4471-01
Task
Change the element in fuel gas filter F-201
Fluid
Fuel gas, flammable. Substance category 2
Duty
15 barg in, 14 barg on the skid side, 10 cm line, 3 to 10 people nearby
Baseline
Release M, location M, outcome B. Category I, positive isolation
Variation
V-0147 authorised for short-duration work: proved double block and bleed each side. Prove every valve, bleeds to flare secured shut, attended throughout, finish inside the shift ¶136
Certificate log
Appendix 6 · paragraphs 115 to 124

What standard does this job start from?

The selection tool turns substance, pressure, line size and location into a baseline standard for the final isolation. It is a floor to reason from. It does not make the decision.

Worked examples from the guidance
Substance category. Tick every one that applies; the highest result wins
Pressure
Line size
Location: who and what is nearby

Do not use the tool for confined space entry, pipelines, extended isolations, or anywhere failure would be catastrophic or hard to recover from ¶116. Near a category boundary, err on the side of caution. Categories follow the CHIP classifications printed in the 2006 edition; CHIP has since been replaced by CLP, so map your substances with care.

Figure 4 · paragraphs 109 to 120

Eight ways to hold a line shut

Three categories, ranked by how sure you can be. Within a category the methods are not equal, and every added component is another chance for error. Filled valves are closed.

Figure 5 · paragraphs 121 to 141

From baseline to a decision

The aim is a risk that is ALARP and tolerable. Meeting the baseline is not the aim. Answer for a job you know and follow where the guidance sends you.

Figure 6 · Appendix 4, table A

Valves and what keeps them shut

A valve is only an isolation if it seals and stays where you left it. Prove leak tightness every time a valve is used for isolation App 4 ¶6.

Security, most to least

MostLocks with the keys held away from the work party, for example in a lockout box, or the actuating mechanism removed. Offshore, onshore high-risk work, remote locations.
MiddleChain or cable lock with a tag referenced to the permit, or a handwheel cover. The work party holds the keys. A plastic tie cuts more easily than a chain.
LeastTag only. No physical security, procedural control alone. Needs tight control of the area, lower hazards and the work party in constant attendance. Fits some own isolations.

Control and choke valves are not generally suitable for isolation. Relief valves only with a purpose-designed way to secure them shut and test them. Emergency isolation valves may serve if the type suits the fluid App 4 ¶2.

Incidents described in the guidance

Seven case files

Each of these happened. Read the facts, then call the failure before you open the lesson.

Ten questions · paragraph references on every answer

Knowledge check

Terms as HSG253 uses them

Glossary